Fire Safety for Data Centers: Clean Agents and Standards

Multiple fire extinguishers lined up on grass, ready for emergency use, showcasing fire safety equipment

A server hall cannot be fought with water like a warehouse: clean-agent systems are the near-default technical choice, but what the law requires is not the name of a gas — it is a chain of design appraisal, acceptance testing and maintenance the project must pass before operating.

Legal basis to know

The Law on Fire Prevention, Fighting and Rescue 55/2024/QH15, effective 1 July 2025, together with detailing Decree 105/2025/ND-CP — amended by Decree 347/2026/ND-CP — governs fire design appraisal, acceptance and operational management for regulated facilities, among which data centers with large power loads and sealed server halls fall into the strict appraisal group. QCVN 06:2022/BXD on fire safety for buildings sets requirements on evacuation, fire compartmentation and technical systems. Decree 105/2025 also carries in its appendix the list of facilities subject to compulsory fire and explosion insurance.

How this applies in practice

Technologically, clean agents such as FM-200 or Novec 1230 are chosen because they suppress fire chemically or by reducing oxygen concentration without destroying electronics the way water and powder do; but a system only complies when concentration design, discharge time, room integrity and interlocks with power and cooling are calculated and accepted as a whole. The common failure is buying internationally certified equipment while the domestic appraisal file does not match the as-built installation, stalling acceptance right before launch.

What to do now

  • Lock the fire design with an appraisal-capable consultant at the basic design stage, avoiding changes after the server hall is built.
  • Keep a three-layer consistent file: appraised design, actually installed equipment and acceptance minutes, plus a periodic room integrity test plan.
  • Write clean-agent maintenance and fire drills into the operations contract, and verify the facility’s compulsory fire and explosion insurance duty.

Frequently Asked Questions

What extinguishes fire in a data center?

Server halls typically use clean-agent systems such as FM-200 or Novec 1230 combined with early smoke detection, because these agents suppress fire without destroying electronics; ancillary areas may use other systems per the appraised design.

Which standards apply?

The standards frame comprises the Law on Fire Prevention, Fighting and Rescue 55/2024/QH15, Decree 105/2025/ND-CP on appraisal and acceptance, QCVN 06:2022/BXD on building fire safety, plus international industry standards such as NFPA 75 and NFPA 2001 used as design references but not substitutes for domestic appraisal.

How does acceptance testing work?

Fire acceptance is performed by the fire police authority based on the appraised design, checking actually installed equipment, test results of detection and suppression systems and interlocked systems; only after a passing acceptance document may the regulated parts of the facility enter operation.

What maintenance is required?

Maintenance includes periodic checks of agent cylinders and pressure, testing of detection and interlock systems on the manufacturer’s and operational schedules, room integrity re-testing after any structural change, and fire drills for the operations team at the statutory frequency.